Control Air L100 Bubble Tube Liquid Level System
The L100 Bubble-Tube Level System is a fully self contained instrument (liquid level system), requiring only connections to air or gas supply, dip tube and electrical power source to provide precise level measurement. Because only the stationary dip tube and the purge gas come in contact with the liquid, this system is ideal for applications involving hazardous locations or liquids which are highly corrosive, viscous, hot, (molten metal), explosive, slurry type or foodstuff. Some of the specific applications include waste and water treatment plants for municipalities and trash to energy plants. In addition, the electronic output from the L100 is compatible with almost all analog instrumentation, including local and remotely-located indicators, computers, data loggers, recorders and controllers.
Request a Quote
Availability:
In stock
SKU
CA02400W
The L100 Bubble-Tube Level System is a fully self contained instrument (liquid level system), requiring only connections to air or gas supply, dip tube and electrical power source to provide precise level measurement. Because only the stationary dip tube and the purge gas come in contact with the liquid, this system is ideal for applications involving hazardous locations or liquids which are highly corrosive, viscous, hot, (molten metal), explosive, slurry type or foodstuff. Some of the specific applications include waste and water treatment plants for municipalities and trash to energy plants. In addition, the electronic output from the L100 is compatible with almost all analog instrumentation, including local and remotely-located indicators, computers, data loggers, recorders and controllers.
SPECIFICATIONS
Input (Air) |
1.0 to 7.0 SCFH, regulated on-board to a pressure of 200% of full scale liquid head. Maximum blow-down pressure is 150 psi. Maximum on-board regulated pressure is 60 psi |
---|---|
Input (Electrical) |
Using P200: 10-42 VDC (units with automatic blow-down and digital readout options also require 120 VAC) |
Electrical Output |
P200: 2 wire, 4-20mA into 700Ω at 24 VDC or 2 wire, 10-50mA into 280Ω at 24 VDC |
Accuracy |
± 0.25% of span guaranteed; ±0.20% of span typical. Includes combined effects of linearity, hysteresis and repeatability errors |
Sensitivity |
±0.02% of span guaranteed |
Repeatability |
±0.10% of span guaranteed; ±0.05% of span typical |
Temperature (Operating) |
30° to 161°F (-1.1° to 72°C) |
Thermal Sensitivity |
Span: 0.007% of span per ˚F guaranteed Zero: 0.007% of span per ˚F guaranteed |
RFI/EMI Effect |
Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter |
Environmental |
Basic Bubble-Tube system mounted on a panel assembly has no environmental protection. Option "E" provides the panel assembly mounted in a NEMA 4X enclosure |